Vsd Data Key; Figure 53 - Vsd Data Key - York YVAA Installation Operation & Maintenance

Air-cooled screw liquid chillers, air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form 201.47-ICOM1
Issue date: 17/11/2022
VSD
data key

Figure 53 - VSD data key

General
The VSD DATA key provides the user with displays of
VSD temperatures, voltages, currents, and other oper-
ating data. This key has multiple displays, which can
be seen by repeatedly pressing the VSD DATA or the
▲ or ▼ (Arrow) keys. An explanation of each mes-
sage is provided.
VSD data key operation
The first VSD DATA key press displays the actual VSD
Output Frequency and Command Frequency.
VSD FREQUENCY
COMMAND = XXX.X HZ
The second key press of the VSD DATA key or the ▼
(ARROW) key displays the calculated compressor %
FLA and measured motor currents in amps for systems
1 and 2. When measuring motor current keep in mind
that measuring inverter PWM current is difficult and
meter error can be significant.
VSD COMP 1 = XXX AMPS
COMP 2 = XXX AMPS
The next key press displays the current limit values
set locally on the panel under the PROGRAM key, re-
motely by a BAS, and remotely by the Current Limit
input. Any current limits that are inactive will display
"XXX" instead of a numeric value.
VSD CURRENT LIMIT
ISN = XXX
JOHNSON CONTROLS

VSD data key

ACTUAL = XXX.X HZ
= XXX %FLA
= XXX %FLA
LOCAL = XXX %FLA
REMOTE = XXX %FLA
The next key press displays DC Bus voltage.
VSD
DC BUS VOLTAGE = XXX VDC
The next key press displays the Control Panel/VSD In-
ternal Ambient Temperature and VSD Cooling Pump/
Fan Status. YYY will indicate ON or OFF.
VSD
INTERNAL AMBIENT TEMP = XXX.X °F
COOLING SYSTEM STATUS = YYY
The next key press displays the IGBT highest baseplate
temperature.
VSD IGBT BASEPLATE TEMPS
The next key press displays the state of the Precharge
signal, where XXX is either ON or OFF.
VSD
PRECHARGE SIGNAL = XXX
The next key press displays the setting of the VSD's
105% FLA overload potentiometer for Compressor #1
and 2. The settings are determined by the adjustment of
the overload potentiometers on the VSD Logic Board.
These pots are factory set and should not require chang-
ing unless the circuit board is replaced.
VSD
COMP 1 MOTOR OVERLOAD = XXX AMPS
COMP 2 MOTOR OVERLOAD = XXX AMPS
SECTION 8 - MICROPANEL
LD10605
T1 = XXX °F
T2 = XXX °F
127
8