Zone Sensor Mode

Volts DC
Ohms
+- 5%
Rx1K
0.00
0.00
0.47
2.32
0.82
4.87
1.09
7.68
1.30
10.77
1.43
13.32
1.54
16.13
1.65
19.48
1.84
27.93
1.94
35.00
2.03
43.45
2.50

Zone Sensor Setpoint

°F
°C
90
32.22
89
31.67
88
31.11
87
30.56
86
30.00
85
29.44
84
28.89
83
28.33
82
27.78
81
27.22
80
26.67
79
26.11
78
25.56
77
25.00
76
24.44
75
23.89
74
23.33
System
Fan
Switch
switch
Short
Short
OFF
AUTO
COOL
AUTO
AUTO
AUTO
OFF
ON
COOL
ON
AUTO
ON
HEAT
AUTO
HEAT
ON
EM HEAT
AUTO
EM HEAT
ON
Open
Open
circuit
circuit
(K ohms)
DCV
0.1106
0.249
0.1301
0.288
0.1495
0.325
0.1689
0.362
0.1884
0.397
0.2079
0.430
0.2273
0.463
0.2468
0.495
0.2663
0.526
0.2858
0.556
0.3053
0.585
0.3247
0.613
0.3442
0.640
0.3637
0.667
0.3832
0.693
0.4026
0.718
0.4221
0.742
°F
°C
73
22.78
72
22.22
71
21.67
70
21.11
69
20.56
68
20.00
67
19.44
66
18.89
65
18.33
64
17.78
63
17.22
62
16.67
61
16.11
60
15.56
59
15.00
58
14.44
57
13.89
56
13.33
55
12.78
54
12.22
53
11.67
52
11.11
51
10.56
50
10.00
49
9.44
48
8.89
47
8.33
46
7.78
45
7.22
44
6.67
43
6.11
42
5.56
41
5.00
40
4.44
58
(K ohms)
DCV
0.4416
0.766
0.4610
0.789
0.4805
0.812
0.5000
0.834
0.5195
0.855
0.5390
0.876
0.5584
0.896
0.5779
0.916
0.5974
0.935
0.6169
0.954
0.6363
0.972
0.6558
0.990
0.6753
1.008
0.6948
1.025
0.7142
1.042
0.7337
1.058
0.7544
1.075
0.7751
1.092
0.7958
1.108
0.8166
1.124
0.8373
1.139
0.8580
1.155
0.8787
1.169
0.8994
1.184
0.9179
1.197
0.9363
1.209
0.9548
1.221
0.9733
1.233
0.9918
1.245
1.0102
1.257
1.0287
1.268
1.0472
1.279
1.0656
1.290
1.0841
1.301