Reliatel Condenser Paired With A Symbio Szvav Air Handler - Trane SYMBIO 700 Troubleshooting Manual

Hide thumbs Also See for SYMBIO 700:
Table of Contents

Advertisement

Reliatel Condenser paired with a Symbio SZVAV Air Handler

Order the following
Harness from Air Handler Relay Board J11 to VFD PPM53 – WIR010190
Harness PPF53 to the VFD – WIR010185
Interconnecting Wiring
Condenser LTB2-R to Air Handler Relay Board J10-1
Condenser LTB1-B to Air Handler Relay Board J10-2
Condenser RTRM J7 (Y2) to Air Handler Relay Board J5-6
Condenser LTB1-EF to Air Handler Relay Board J5-4
Condenser LTB1-H1 to Air Handler Relay Board J5-7 - Electric Heat
Condenser LTB1-H2 to Air Handler Relay Board J5-8 - Electric Heat
EDC Switch - Optional
Condenser LTB2-CD to Air Handler Relay Board J5-1
Move wire from terminal "H" to terminal "L" on EDC switch, enabling normally closed switch operation.