Connections between Condenser and Air Handler (if using EDC add 2 more wires)
1.
Thermostat Wire – 5 Wires w/o electric heat, 7 Wires with electric heat
a.
Symbio Condenser Adapter Board J15-1 to Air Handler LTB2-R.
b.
Symbio Condenser Adapter Board J15-2 to Air Handler LTB2-B1.
c.
Symbio Condenser Adapter Board J18-1 to Air Handler Relay Board J5-4
d.
Symbio Condenser UC J21-2 to Air Handler Relay Board J5-5
e.
Symbio Condenser UC J21-6 to Air Handler Relay Board J5-6
f.
Symbio Condenser UC J21-3 to Air Handler LTB2-W1
g.
Symbio Condenser UC J21-5 to Air Handler LTB2-W2
Connections inside Air Handler
2.
Thermostat Wire
a.
Air Handler LTB2-R to Relay Board J10-1
b.
Air Handler LTB2 –B1 to Relay Board J10-2
c.
Air Handler LTB2-W1 to Relay Board J5-7
d.
Air Handler LTB2-W2 to Relay Board J5-8
3.
VFD Programming
a.
5-40 Function Relay – [0] (Relay 1) [6] Running / no warning (Relay 2)
4.
Symbio Configuration
a.
System Type: CVZT
b.
Indoor Fan Type: Single Speed
5.
Fan Interlock Wiring for Electric Heat
a.
Add a field wire from VFD Relay 2, Terminal 5 to LTB2-B1.
b.
Move the Brown wire (from the Electric Heat Accessory) from LTB1-J to VFD Relay 2, Terminal 4.
154