Trane SYMBIO 700 Troubleshooting Manual page 150

Hide thumbs Also See for SYMBIO 700:
Table of Contents

Advertisement

TR-150 Drive
Remove the existing wire harness from Relay Board P1 to VFD terminals 61, 68 and 69.
Install WIR010190 and WIR010185 following the diagram below.
TR-150 Drive Parameters
Change 3-15 from Local Bus to Analog Input 53
Change 5-10 from No Operation to Start
Change 5-12 from No Operation to Coast Inverse
Change 8-01 from Control Word Only to Digital and Control Word
Change 8-02 from FC Port to None
Verify 4-12 is set to 25 HZ
Verify 4-14 is set to 60 HZ
Verify 6-10 is set to 0.07V
Verify 6-11 is set to 10.00V
Verify 6-14 is set to 25 HZ
Verify 6-15 is set to 60 HZ