Installation - Omron D4BL Manual

Safety-door lock switch
Hide thumbs Also See for D4BL:

Advertisement

D4BL

Installation

H
PROCEDURE FOR CONNECTING CABLE
The following procedure is recommended so that the D4BL can be
wired or connected to the Indicator Units with ease.
Recommended connecting cable:
AWB20 to AWG18 with seven conductors
A UL2464-style cable is recommended.
Apply sealing tape to the cable and conduit opening so that the
D4BL can conform to IP67. Tighten the connector to a torque of 1.8
to 2.2 NSm (15.93 to 19.47 in lbs).
Connect the Indicator Units to the D4BL after connecting the 7-con-
ductor cable to the D4BL.
Terminal no.
E
1
E
2
31
12
23 (21)
24 (22)
Ground
Downloaded from
Elcodis.com
electronic components distributor
a
Lv
Lp
a
Lp mm (inch)
Lv mm (inch)
a mm (inch)
30 2
80 2
8 1
(1.18 0.08)
(3.15 0.08)
(0.31 0.08)
35 2
75 2
(1.38 0.08)
(2.95 0.08)
45 2
60 2
(1.77 0.08)
(2.36 0.08)
55 2
50 2
(2.17 0.08)
(1.97 0.08)
65 2
45 2
(2.56 0.08)
(1.77 0.08)
70 2
35 2
(2.76 0.08)
(1.38 0.08)
90 2
50 2
(3.54 0.08)
(1.9 0.087)
Cable Connecting Example
1. As shown in the following illustration, the wires must be
connected in sequence beginning with the terminal nearest to
the conduit opening.
A
E
E
31 12 23 24
1
2
The wire leads must be wrapped around the screws clockwise.
Tighten each screw to a torque of 0.5 to 0.7 NSm (4.43 to 6.20 in lbs).
2. The external insulation sheath of the 7-conductor cable must
contact with side A or B as shown in the above D4BL
illustration.
Edge of insulation sheath
D4BL
B
11

Advertisement