Carrier CHS183-243 Installation Instructions Manual page 7

Heat pump condensing units with r-410a refrigerant
Table of Contents

Advertisement

NOMINAL CAPACITY (kW)
OPERATING WEIGHTS (kg)
Aluminum-Fin Coils
REFRIGERATION SYSTEM
No. Circuits / No. Comp. / Type
Shipping Charge A/B (kg)
System Charge with Fan Coil
Metering Device
High-Press. Trip / Reset (kPa)
Low-Press. Trip / Reset (kPa)
COMPRESSOR
Model
Oil Charge A/B (L)
Speed (r/s)
OUTDOOR COIL
Material
Coil Type
Rows/Fins Per Meter
Total Face Area (m
2
)
OUTDOOR FAN / MOTOR
Qty / Motor Drive Type
Motor hp / r/s
Fan Diameter (mm)
Nominal Airflow (L/s)
Watts (total)
Cut-in
PIPING CONNECTIONS (mm ODS)
Qty / Vapor
Qty / Liquid
NOTE(S):
a
Approximate system charge with 7.6 m piping of sizes indicated with matched FHX.
LEGEND
ODS
Outside Diameter Sweat (socket)
RTPF
Round Tube/Plate Fin
CHS-180-240-01SI Rev. A
Table 3 — Physical Data — CHS183-243 Units — 60 Hz SI
UNIT
a
A/B (kg)
Specifications subject to change without notice.
CHS183*T/U
52.8
348
R-410A
2 / 2 / Scroll
4.1 / 4.1
12.8 / 12.1
Acutrol
4344 / 3482
27 / 44
ZPS83/ZP83
1.6 / 1.7
58
Al/Cu
RTPF
2 / 17
4.4
3 / Direct
1/4 / 18
559
4719
970
44 ±5
2 / 34.9
2 / 12.7
CHS243*T/U
70.3
460
R-410A
2 / 2 / Scroll
4.1 / 4.1
12.2 / 12.2
Acutrol
4344 / 3482
27 / 44
ZPS104/ZP104
2.4 / 2.4
58
Al/Cu
RTPF
2 / 17
4.6
4 / Direct
1/4 / 18
559
6607
1150
44 ±5
2 / 34.9
2 / 12.7
7

Advertisement