Installation; Jobsite Survey; Step 1 - Plan For Unit Location; Step 2 - Complete Pre-Installation Checks - Carrier CHS183-243 Installation Instructions Manual

Heat pump condensing units with r-410a refrigerant
Table of Contents

Advertisement

INSTALLATION

Jobsite Survey

Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installa-
tion requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (pad,
rails or other) that provides for the minimum clearances re-
quired for safety. This includes the clearance to combustible
surfaces, unit performance and service access below,
around and above unit as specified in unit drawings. See
Fig. 4.
Select a unit mounting system that provides adequate
height to allow for removal and disposal of frost and ice that
will form during the heating-defrost mode.
NOTE: Consider also the effect of adjacent units on airflow
performance and control box safety clearance.
Do not install the outdoor unit in an area where fresh air
supply to the outdoor coil may be restricted or when recircu-
lation from the condenser fan discharge is possible. Do not
locate the unit in a well or next to high walls.
Evaluate the path and required line length for interconnect-
ing refrigeration piping, including suction riser requirements
(outdoor unit above indoor unit), liquid line lift (outdoor unit
below indoor unit) and hot gas bypass line. Relocate sec-
tions to minimize the length of interconnecting tubing.
IMPORTANT: DO NOT BURY REFRIGERATION
LINES.
Although unit is weatherproof, avoid locations that permit wa-
ter from higher level runoff and overhangs to fall onto the unit.
REAR:
Min 18" (457 mm)
required for service
LEFT:
Min 18" (457 mm)
required for service
NOTE: Observe requirements for 39" (914 mm) operating clearance
on either Left or Rear coil opening.
Fig. 4 — Service Clearance Dimensional Drawing
Step 2 — Complete Pre-Installation Checks

CHECK UNIT ELECTRIC CHARACTERISTIC

Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.

UN-CRATE UNIT

Remove unit packaging except for the top skid assembly,
which should be left in place until after the unit is rigged into
its final location.
CHS-180-240-01SI Rev. A
RIGHT:
Min 18" (457 mm)
required for service
FRONT:
42" (1067 mm)
required for service
Specifications subject to change without notice.

INSPECT SHIPMENT

File a claim with shipping company if the shipment is dam-
aged or incomplete.

CONSIDER SYSTEM REQUIREMENTS

Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
Allow sufficient space for airflow clearance, wiring, re-
frigerant piping, and servicing unit. See Fig. 1 and 2
for unit dimensions and weight distribution data.
Locate the unit so that the outdoor coil (condenser)
airflow is unrestricted on all sides and above.
The unit may be mounted on a level pad directly on
the base channels or mounted on raised pads at sup-
port points. See Tables 2 and 3 for unit operating
weights. See Fig. 1 and 2 for weight distribution
based on recommended support points.
NOTE: If vibration isolators are required for a particular in-
stallation, use the data in Fig. 1 and 2 to make the proper
selection.
Step 3 — Prepare Unit Mounting Support

SLAB MOUNT

Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron in
front of condenser coil air inlet to prevent grass and foliage
from obstructing airflow.
Step 4 — Rig and Mount the Unit

RIGGING

These units are designed for overhead rigging. Refer to the
rigging label for preferred rigging method. Spreader bars are
not required if top crating is left on the unit. All panels must
be in place when rigging. As further protection for coil faces,
plywood sheets may be placed against the sides of the unit,
behind cables. Run cables to a central suspension point so
that the angle from the horizontal is not less than
45 degrees. Raise and set the unit down carefully.
If it is necessary to roll the unit into position, mount the unit
on longitudinal rails, using a minimum of 3 rollers. Apply
force to the rails, not the unit. If the unit is to be skidded into
position, place it on a large pad and drag it by the pad. Do
not apply any force to the unit.
Raise from above to lift the unit from the rails or pad when
unit is in its final position.
After the unit is in position, remove all shipping materials
and top crating.
Step 5 — Complete Refrigerant Piping

Connections

Refrigerant lines must be carefully designed and construct-
ed to ensure equipment reliability and efficiency. Line
length, pressure drop, compressor oil return, and vertical
separation are several of the design criteria that must be
evaluated. See Table 4.
IMPORTANT: Do not bury refrigerant piping under-
ground.
IMPORTANT: A refrigerant receiver is not provided with
the unit. Do not install a receiver.
9

Advertisement

Table of Contents
loading

Table of Contents