Avoid the use of:
coil brighteners
acid cleaning prior to painting
high pressure washers
poor quality water for cleaning
Totaline environmentally sound coil cleaner is nonflamma-
ble, hypoallergenic, non bacterial, and a USDA accepted
biodegradable agent that will not harm the coil or surround-
ing components such as electrical wiring, painted metal sur-
faces, or insulation. Use of non-recommended coil cleaners
is strongly discouraged since coil and unit durability could
be affected.
Totaline Environmentally Sound Coil Cleaner
Application Equipment:
2-1/2 gallon garden sprayer
Water rinse with low velocity spray nozzle
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in corrosion and
damage to the unit.
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult to
rinse out of the coil and can accelerate corrosion at the
fin/tube interface where dissimilar materials are in con-
tact. If there is dirt below the surface of the coil, use the
Totaline environmentally sound coil cleaner as described
above.
CAUTION
UNIT RELIABILTY HAZARD
Failure to follow this caution may result in reduced unit
performance
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to clean
a coil. The force of the water or air jet will bend the fin
edges and increase airside pressure drop.
Totaline Environmentally Sound Coil Cleaner
Application Instructions:
NOTE: Proper eye protection such as safety glasses is rec-
ommended during mixing and application.
1. Turn off unit power.
2. Remove screws holding rear corner post and top
cover in place. Pivot top cover up 12 to 18 inches
(305 to 457 mm) and support with a rigid support.
See Fig. 28.
CHS-180-240-01SI Rev. A
3. Remove all surface loaded fibers and dirt with a vac-
NOTE: Use of a water stream, such as a garden hose,
against surface loaded coil will drive the fibers and dirt into
the coil, making cleaning efforts more difficult. Surface load-
ed fibers must be completely removed prior to using low ve-
locity clean water rinse.
4. Using a low velocity garden hose thoroughly wet
5. Mix Totaline environmentally sound coil cleaner in a
NOTE: Do NOT USE water in excess of 130°F (54°C), as
the enzymatic activity will be destroyed.
6. Thoroughly apply Totaline environmentally sound coil
7. Hold garden sprayer nozzle close to finned areas
8. Ensure cleaner thoroughly penetrates deep into
9. Interior and exterior finned areas must be thoroughly
10. Finned surfaces should remain wet with cleaning
11. Ensure surfaces are not allowed to dry before rins-
12. Thoroughly rinse all surfaces with low velocity clean
13. Replace top cover and rear corner posts.
Specifications subject to change without notice.
Top
Cover
Fig. 28 — Pivot and Support Top Cover
uum cleaner. If a vacuum cleaner is not available, a
soft non-metallic bristle brush may be used. In either
case, the tool should be applied in the direction of the
fins. Coil surfaces can be easily damaged (fin edges
can be easily bent over and damage to the coating of
a protected coil) if the tool is applied across the fins.
finned surfaces with clean water. Be careful not to
bend the fins.
2-1/2 gallon garden sprayer according to the instruc-
tions included with the cleaner. The optimum solution
temperature is 100°F (38°C).
cleaner solution to all coil surfaces including the
finned area, tube sheets and coil headers.
and apply cleaner with a vertical, up-and-down
motion. Avoid spraying in horizontal pattern to mini-
mize potential for fin damage.
finned areas.
cleaned.
solution for 10 minutes.
ing. Reapply cleaner as needed to ensure 10-minute
saturation is achieved.
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Rigid