Air Damper Adjustment; Electrode Setting - Riello F10 INCINERATOR TL Installation, Use And Maintenance Instructions

Gas oil, bio fuel and kerosene burners continuous vent - blinding relay - 50/60hz
Table of Contents

Advertisement

8.6

Air damper adjustment

The values stated in the table are necessary for the first setting
of air-damper.
They are relevant to a burner with mounted cowling and combus-
tion chamber with depression zero.
These values should be adjusted, on the basis of the specific re-
quirements of the system, so that the Bacharach number is not
near 1.
When the burner works at a firing rate higher than 9 kg/h remove
the panel 1)(Fig. 19) fitted inside the metal cover.
The settings indicated in the refer to the burner with its metal cov-
er fitted and the combustion chamber with "zero" depression.
These regulations are purely indicative.
Each installation however, has its own unpredictable working
conditions: actual nozzle output; positive or negative pressure in
the combustion-chamber, the need of excess air, etc.
It is important to take account of the fact that the
air output of the fan differs according to whether
the burner has its metal cover fitted or not. All
WARNING
these conditions may require a different air-damp-
er setting.
8.7

Electrode setting

The position of the electrodes cannot be regulat-
ed. In case of failure, check that the measure-
ments as shown on the figure are respected.
WARNING
20098581
Start-up, calibration and operation of the burner
4 ± 0.3 mm
D5288
A
Therefore we recommend to proceed as follows:
 adjust the air damper as indicated in the ;
 mount the cover, simply by means of the upper screw;
 check smoke number;
 should it become necessary to modify the air output, remove
the cover by loosening the screw, adjust the air damper,
remount the cover and finally re-check the smoke number.
T
D5287
Before removing or assembling the nozzle, loosen the screw
A)(Fig. 20) and move the electrodes ahead.
Move the electrode holder
backwards to the end
22
GB
4.5 ± 12.5 mm
1
Fig. 19
Fig. 20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F20 incinerator tl2009675020096751