COMBUSTION HEAD ADJUSTMENT

Loosen the screw (A), move the elbow (B) so that
the rear plate of the coupling (C) coincides with the
set point.
Tighten the screw (A).
Example:
The burner is installed in a 40 kW boiler.
Considering efficiency of 90% the burner must
supply around 44 kW.
The diagram shows that for this
output the adjustment must be
made on notch 3.
The diagram is to be used only
for initial settings, to improve air
pressure
switch
operation
improve combustion, it may be
necessary to reduce this setting
(set point toward position 0).

AIR DAMPER ADJUSTMENT

The regulation of the air-rate is made by adjusting the air damper
(1), after loosing the screws (2).
When the optimal regulation is reached, screw tight the screws
(2).