8.4

Pump pressure

The pump leaves the factory set for kerosene working.
10 bar: maximum pressure for kerosene.
8.5

Air damper adjustment

The air damper is set in factory. This regulation is purely indica-
tive.
Each installation however, has its own unpredictable working
conditions: actual nozzle output; positive or negative pressure in
the combustion-chamber, the need of excess air, etc.
8.6

Electrodes setting

The position of the electrodes cannot be regulat-
ed. In case of failure, check that the measure-
ments as shown on the figure are respected.
WARNING
Before removing or assembling the nozzle, loosen the screw (A,
Fig. 20) and move the electrodes ahead.
4 ±
0.3 mm
A
D5230
20035274
Start-up, calibration and operation of the burner
2 - 2.5
mm
Fig. 20
All these conditions may require a different air damper setting.
20
GB

Advertisement