Start-up, calibration and operation of the burner

8.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
WARNING
tions of the laws in force.
8.2

Combustion adjustment

In conformity with Efficiency Directive 92/42/EEC the application
of the burner on the boiler, adjustment and testing must be car-
ried out observing the instruction manual of the boiler, including
verification of the CO and CO
their temperatures and the average temperature of the water in
the boiler.
R40 F10 TC/TL
Nozzle
GPH
Angle
1.10
60°
1.25
60°
1.50
60°
1.75
60°
2.00
60°
2.00
60°
1.50
60°
1.75
60°
2.00
60°
2.25
60°
2.50
60°
3.00
60°
3.00
60°
R40 F20 TC/TL
Nozzle
GPH
Angle
2.00
60°
2.25
60°
2.50
60°
3.00
60°
3.50
60°
3.50
60°
2.50
60°
2.75
60°
3.00
60°
3.50
60°
4.00
60°
4.50
60°
5.00
60°
5.50
60°
5.50
60°
20098581
Start-up, calibration and operation of the burner
concentration in the flue gases,
2
Pump
pressure
bar
12.5
12.0
12.0
12.0
12.0
15.0
8.0
8.0
8.0
8.0
8.0
8.0
10
Pump
pressure
bar
12
12
12
12
12
14
9.5
8.0
8.0
8.0
8.0
8.0
8.0
8.0
10
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
To suit the required appliance output, fit the nozzle then adjust
the pump pressure, the setting of the combustion head and the
air damper opening in accordance with the following.
The values shown in the table are measured on a CEN boiler (as
per EN 267). They refer to 12.5% CO
oil and room temperature of 20 °C.
Combustion head
Burner output
kg/h ± 4%
4.5
5.0
6.0
7.0
8.0
9.0
4.43
5.17
5.91
6.64
7.38
8.86
9.99
Burner
output
kg/h ± 4%
8.59
9.66
10.73
12.88
15.03
16.33
7.95
8.60
9.40
10.05
11.00
12.30
14.60
16.45
18.10
20
GB
at sea level and with gas
2
adjustment
Set point
2.0
2.5
3.0
4.0
5.0
6.0
1.5
2.0
2.5
3.5
4.0
5.0
6.0
Combustion head
adjustment
Set-point
1.5
2.0
2.5
3.0
4.0
6.0
1.0
1.0
1.5
2.0
2.5
3.5
5.0
6.0
6.0
Air damper
adjustment
Set point
3.2
4.5
6.0
6.5
7.0
8.0
2.6
2.9
3.3
3.5
3.8
5.0
6.0
Tab. H
Air damper
adjustment
Set-point
3.5
4.7
5.0
6.5
7.0
8.0
2.3
2.6
2.9
3.5
4.0
4.8
5.8
6.0
8.0
Tab. I