Parameters

5.3 Module/channel parameters

Description
The parameters are divided into three types:
• Module/channel parameters (data record 128)
• Parameters which determine the display of HART variables in the address space of the
module; HART mapping parameters (data record 130)
• System parameters (potential group, IO redundancy)
Note
With the exception of parameter assignment of the potential group, all parameters can be
changed when the CPU is in RUN.
5.3
Module/channel parameters
Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channels.
Description
The following module/channel parameters are available:
Parameter
Diagnostics, Missing sup‐
ply voltage L+ (Page 21)
IO redundancy (Page 21)
Potential group
(Page 22)
Output type/range
(Page 22)
Number of HART repeti‐
tions (Page 24)
20
Value range
Enabled
Disabled
None
2 modules
Use potential group of the left
module (dark gray TB)
Form a new potential group (light
gray TB)
No potential group (black TB)
Disabled
Current 0 to 20 mA
Current 4 to 20 mA
Current 4 to 20 mA HART
0...10
Default
Configuration in
Enabled
Yes
None
Yes
Use potential
No
group of the left
module
Current 4 to 20
Yes
mA HART
5
Yes
Equipment Manual, 07/2022, A5E50102497-AB
Efficiency
RUN
range
Module
Module
Module
Channel
Channel
AQ 4xI HART ISOL HA