Output Areas; Figure 5-1 Example Diagram Of Settling Time Without Hart Communication - Siemens SIMATIC ET 200SP HA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

You can choose between different output areas with an active channel.
Note
Unused channels
Disable unused channels in the configuration to improve the cycle time of the module.
A deactivated channel always returns the output value 0 mA.
An overview of the output area, overflow and overrange etc. can be found in the appendix
"Representation of analog values in the current output ranges (Page 75)".
Description
The I/O module has the following output areas:
Table 5-1
Output type
Disabled
Current
Current
Current
View
The settling time depends on whether HART communication is activated for the output area.
You can find the settling time without HART communication (x ms) in section "Technical
specifications (Page 45)".
The settling time without HART communication is represented as follows:
Figure 5-1
If HART communication is activated for the output area, the settling time of the output value is
set to 50 ms.
The settling time with HART communication is represented as follows:
AQ 4xI HART ISOL HA
Equipment Manual, 07/2022, A5E50102497-AB

Output areas

Output range
-
0 to 20 mA
4 to 20 mA
4 to 20 mA HART
Example diagram of settling time without HART communication
5.4 Explanation of the module/channel parameters
Parameters
Resolution
-
15 bits
15 bits
15 bits
23