Parameters

6.1

Parameter types

Definition
You define and thereby influence the functions supported by the module operation of the I/O
module via the parameter types.
6.2

Module/channel parameters

Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channel.
Description
The following module/channel parameters are available:
Parameters
Diagnostics, Missing supply
voltage L+ (Page 20)
Channel activated
(Page 20)
Reaction to CPU STOP
(Page 20)
Substitute value (Page 20)
Potential group (Page 21)
Only in effect when "Substitute value" has been enabled for the "Reaction to CPU STOP" parameter.
1
RQ 4x120VDC-230VAC/5A CO HA
Equipment Manual, 07/2022, A5E39389042-AF
Value range
Enabled
Disabled
Enabled
Disabled
Turn off
Keep last value
Output substitute value
1
0
1
Use potential group of the left
module
Allow new potential group
Default
Parameter re‐
assignment in
RUN
Disabled
Yes
Enabled
Yes
Turn off
Yes
0
Yes
Use potential
No
group of the left
module
6
Efficiency range
Module
Channel
Channel
Channel
Module
19