SEAL & SPACER TOOLS &
REPLACEMENT continued
Figure 9
12. To restuff a valve body, first take the end ring (the plastic or
brass ring without holes), then with your thumb press the
button on the brass sleeve end. The large dia. inner portion
is now exposed (see Figure 8). Place the end ring on this
pilot with the lip on the end ring facing the tool. Push the
tool into the valve body bore until it bottoms. While the tool
is in the valve body, take a seal and press it into the inside
diameter of the exposed brass female end.
13. Remove the tool, turn it end for end and insert it into the
valve body bore. While holding the large dia. of the tool,
slide it all the way into the valve body bore until it bottoms.
Then push the center button to push the seal of the tool and
leave it in place in the valve body.
14. Remove the tool from the valve body and push the center
on the brass female end to expose the pilot on the opposite
end. Place a spacer on this end and insert the spacer and
tool into the valve.
GENERAL SERVICE HINTS FOR METER
CONTROL
Problem: Softener delivers hard water
Reason: Reserve capacity has been exceeded.
Correction: Check salt dosage requirements and reset
program wheel to provide additional reserve.
Reason: Program wheel is not rotating with meter output.
Correction: Pull cable out of meter cover and rotate manually.
Program wheel must move without binding and clutch must
give positive clicks when program wheel strikes regeneration
stop. If it does not, replace timer.
Reason: Meter is not measuring flow.
Correction: Check meter with meter checker.
Fleck 2510 & 2510 Econominder JA12 • 23