Siemens SENTRON VL Series System Manual page 79

Circuit breakers with communication capability - profibus
Hide thumbs Also See for SENTRON VL Series:
Table of Contents

Advertisement

Switch position "P"
If the rotary coding switch is at the "P" position, the measured values of the power are output
via the four channels:
A01: Active power phase P
A02: Active power phase P
A03: Active power phase P
A04: Total apparent power S
To calculate the full-scale deflection value of the active power per phase, the value of the
rating plug must be multiplied by the rated voltage of the system. The full-scale deflection
value is then subdivided into a value range shown in the table below.
For the total apparent power and the total active power (position f), the calculated value still
has to be multiplied by 3 before the full-scale deflection value can be read from the table.
The table below gives the value ranges for power [W/VA]:
Table 3- 20
From
0
50.000
100.000
200.000
300.000
400.000
500.000
1.000.000
2.000.000
3.000.000
5.000.000
10.000.000
20.000.000
Example:
I
= 1600 A, rated voltage = 400 V; ⇒ Full-scale deflection value = 1,000,000 W
R
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
L1
L2
L3
total
Value ranges for power [W/VA] on the analog output module
To
49.999
99.999
199.999
299.999
399.999
499.999
999.999
1.999.999
2.999.999
4.999.999
9.999.999
19.999.999
3WL air circuit breakers
3.5 External CubicleBUS modules
Full-scale deflection value
50.000
100.000
200.000
300.000
400.000
500.000
1.000.000
2.000.000
3.000.000
5.000.000
10.000.000
20.000.000
30.000.000
79