3WL air circuit breakers
3.5 External CubicleBUS modules
Connection of the CubicleBUS without COM15
The figure below shows the connection of external CubicleBUS modules to the
SENTRON WL without COM15.
● Make the first connection with four wires.
● Connect the CubicleBUS with RJ45 connectors using the supplied CubicleBUS cables.
● Connect the power supply to the X3 interface.
Only with more than 2 CubicleBUS modules: Connecting cable between X8 and the first CubicleBUS module for
power supply with 24 V DC
Connecting cables between the modules
Terminating resistor 120 Ω 0.5 W on the last module
CubicleBUS modules
Cable connection for power supply with 24 V DC
Figure 3-15
Connection of the CubicleBUS without COM15
62
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02