Siemens SENTRON VL Series System Manual page 267

Circuit breakers with communication capability - profibus
Hide thumbs Also See for SENTRON VL Series:
Table of Contents

Advertisement

Table 8- 61
The table below shows the format (129) "Configurable output module". Event 1 of the 1st
output provides an example of the assignment for all others.
Table 8- 62
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
Format (121) "Control DO outputs"
Byte
Value
0
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
0
11
0
12
0
13
Format (129) "Configurable output module"
Byte
Value
0
0
0x00
0
0x01
0
0x02
0
0x03
0
0x04
0
0x05
0
0x06
0
0x07
0
0x08
0
0x09
0
0x0A
0
0x0B
0
0x0C
0
0x0D
0
0x0E
0
0x0F
0
0x10
0
0x11
0
0x12
0
0x13
No action
Set output 1 ("1")
Reset output 1 ("0")
Set output 2 ("1")
Reset output 2 ("0")
Set output 3 ("1")
Reset output 3 ("0")
Set output 4 ("1")
Reset output 4 ("0")
Set output 5 ("1")
Reset output 5 ("0")
Set output 6 ("1")
Reset output 6 ("0")
Switch force mode off (overwriting of the actually valid data)
1. event at the 1st output
Not assigned
Switch on
Switch off
Spring energy store compressed
Ready for switching on
General warning
Group tripped signal
DP write protection active
DP communication OK
Alarm: Overload
Alarm: Overload N-conductor
Alarm: Load shedding
Alarm: Ground fault
Alarm: Overtemperature
Alarm: µP-Error
Alarm: Phase unbalance Current
Alarm: Load pick up
Trip: Overload L
Trip: Delayed short-circuit I
Trip: Instantaneous Short-circuit S
Meaning
Meaning
Data library
8.7 Formats
267