Third party components

4 Third party components

4.1 Electrical circuit

4.1.1 Checking procedures

To check the power supply of the unit
To check the power supply to the indoor unit
Service manual
128
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Check that the power supply cables and earth connection are firmly fixed to
the power supply terminal X1M.
2 Measure the insulation resistance between each power supply terminal and
the ground using a megger device of 500  V  DC. All measurements MUST be
>1MΩ. If insulation resistance is <1MΩ, earth leakage is present.
3 Turn ON the power of the unit.
4 Measure the voltage between L and N on the power supply terminal X1M.
Result: The voltage MUST be 230 V AC ± 10%.
5 Unbalance between the phases MUST NOT exceed 2%.
Is the measured voltage (power supply)
correct?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see
2 Check that the power supply cables and earth connection are firmly fixed to
the indoor unit power supply terminal X1M.
3 Turn ON the power using the respective circuit breaker.
4 Measure the voltage between L and N on the indoor unit power supply
terminal X1M.
Result: The voltage MUST be 230 V AC ± 10%.
Is the measured voltage (power supply)
correct?
Yes
No
5 Check the power supply to the unit, see
"3.10 Plate
work" [
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Adjust the power supply, see
"4.1.2 Repair
procedures" [
4
"3.10 Plate
work" [
 100].
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Continue with the next step.
"4.1.1 Checking
procedures" [
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
4
 100].
4
 129].
4
 128].
Split Comfora R32
ESIE18-01D – 2022.02