Reading I&M data via STEP 7
Requirements: An online connection to the CPU must exist.
To read the I&M data via STEP 7, follow these steps:
1. In the project tree, select the CPU 1516pro-2 PN .
2. Go to "Online & diagnostics".
3. Select the "General" area in the "Diagnostics" folder.
Enter maintenance data via STEP 7
STEP 7 assigns a default module name. You can enter the following information:
● Plant designation (I&M1)
● Location identifier (I&M1)
● Installation date (I&M2)
● Additional information (I&M3)
To enter maintenance data via STEP 7, follow these steps:
1. In the device view of the hardware network editor of STEP 7, select the CPU, for
example.
2. Go to properties, "General", and select the "Identification & Maintenance" area.
3. Enter the data.
During the loading of the hardware configuration, the I&M data is also loaded.
Reading I&M data via the Web server
The procedure is described in detail in the Web server
(https://support.industry.siemens.com/cs/ww/en/view/59193560) Function Manual.
CPU 1516pro-2 PN (6ES7516-2PN00-0AB0)
Operating Instructions, 11/2019, A5E35873416-AC
8.7 Identification and maintenance data