Commissioning procedure
To commission the ET 200pro distributed I/O system as I-device on PROFINET IO, proceed
as follows:
Table 8- 2
Procedure for commissioning the ET 200pro as an I-device on PROFINET IO
Step
Procedure
1
Mounting ET 200pro (with CPU 1516pro-2 PN)
2
Inserting the SIMATIC memory card into the I-device
3
Connecting the ET 200pro
Supply voltages
•
PROFINET IO
•
Sensors and actuators
•
4
Configuring the I-device
5
Switch on supply voltages for the IO controller
6
Switch on supply voltages for I-device and IO devices
7
Download configuration to the I-device
8
Switch IO controller and I-device to RUN mode
9
Check LEDs
10
Test inputs and outputs
CPU 1516pro-2 PN (6ES7516-2PN00-0AB0)
Operating Instructions, 11/2019, A5E35873416-AC
8.2 Procedure for commissioning the ET 200pro distributed I/O system with CPU
See ...
Section Mounting and connecting (Page 23)
Operating instructions ET 200pro Distributed I/O
System
(https://support.industry.siemens.com/cs/ww/en/view/
21210852)
Section Inserting/replacing SIMATIC memory card
(Page 76)
Operating instructions ET 200pro Distributed I/O
System
(https://support.industry.siemens.com/cs/ww/en/view/
21210852)
Section Configuring the CPU (Page 34)
Documentation of the IO controller
Section Mounting and connecting (Page 23) and
documentation of the IO devices
STEP 7 online help
Documentation of the IO controller and section RUN
mode (Page 81)
Section Interrupts, diagnostics, error messages and
system events (Page 114)
The following functions are helpful: Monitoring and
modifying tags, testing with program status, forcing,
controlling the outputs. See section Test and service
functions (Page 105)
Commissioning