Connect Input/Output (I/O) Signals
Electric EEO Option
1. Plug the EEO bulkhead fitting (J) on the cabinet
with a 5/32 in. plug (18).
2. Run a signal wire and a ground wire through the I/O
strain relief ports on the right side of the system.
See F
. 7.
IG
3. Feed these wires through the top right opening in
the electronics control panel.
4. Connect terminal block 11 (C11) to the gun's
electrostatic controller with the signal wire.
-
When the output is inactive terminal block 11
(C11) has 4-5V present.
-
When the output is active there is 24V present.
5. Connect terminal block 12 (C12) to the ground wire.
NOTE: Terminal block 11 (C11) signal voltage is
optically isolated at Graco electrostatic controllers. If
using any other controller be sure to use an
optocoupler at the input to the device.
NOTICE
To prevent damage to equipment, do not use these
terminal blocks without an optocoupler present.
10

Wire LPO Optocoupler

1. LPO optocoupler (B) ports A1+ and A2– are wired
to the control module.
2. Wire LPO optocoupler (B) ports 13+ and 14 to an
external device or PLC.
F
. 9 Low paint output wiring
IG
A1+ (relative to
Function
Low Paint Output
24 VDC
Active
Low Paint Output
Less than 13.5
Inactive
VDC
A2–)
PLC
13+ and 14
connected
13+ and 14 not
connected
3A8812B