Installing An Energy Pack - HP ProLiant ML30 Gen10 Plus User Manual

Hide thumbs Also See for ProLiant ML30 Gen10 Plus:
Table of Contents

Advertisement

Installing an energy pack

Installing an energy pack
Prerequisites
Prerequisites
Make sure that a compatible type-p storage controller is installed .
Make sure that you have the following items available:
Storage controller backup power cable (ships with the storage controller)
Energy pack holder option (786710-B21)
If you are installing the HPE Smart Storage Hybrid Capacitor, verify that the system meets the minimum firmware requirements .
Procedure
Procedure
1. Power down the server.
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Disconnect all peripheral cables from the server.
4. Do one of the following:
If the server is in tower mode, place the server on a flat, level surface with the access panel facing up.
If the server is in rack mode, remove the server from the rack .
5. Remove the access panel .
6. If installed, remove the air baffle .
7. Install the energy pack holders:
a. Remove the tapes that cover the installation location for the energy pack.
Installing an energy pack
128