Anti-Condensation Function - Mitsubishi Electric i-BX-N Technical Manual

Table of Contents

Advertisement

TM_i-BX(-N)_NC05_00_06_20_EN
4.3

ANTI-CONDENSATION FUNCTION

The management of this function requires the zone N-THC thermostat.
When the system is set to cooling, excessive ambient humidity may cause the formation of condensation.
This can be counteracted by increasing the delivery water temperature proportionally with the humidity increase detected in the environment (see the
following chart).
The function is enabled using the parameter (0156 for the system, 0171 for the mixed zone), if the system cooling climate curve (0154) is enabled.
If the relative humidity, measured by the ambient thermostat, exceeds the value set at parameter 0157 (for the low zone: 0172) the water setpoint
increases until it reaches the maximum temperature. The maximum water temperature is the result of the sum of the setpoint calculated according
the cooling climate curve and the value set in parameter 0158 (for the low zone: 0173).
For the default values of the various parameters, see the parameters table
Using the parameter it is possible to configure a digital output as dehumidifier control. The "external" dehumidifier is activated if the humidity detected
by the zone thermostat probe exceeds the value set in parameter 0172.
MEHITS S.p.A.
TECHNICAL MANUAL
Delivery
offset
Max.
value
0158
0173
Offset start RH%
0157
0172
100% RH%
Amb. Hum. RH%
34
Version NC05 - Translation of the Original Instructions