Menù 03; Menù 04; Menù 05 - Mitsubishi Electric i-BX-N Technical Manual

Table of Contents

Advertisement

TM_i-BX(-N)_NC05_00_06_20_EN
2.4.4
MENÙ 03
Num Par
Description
P0300
Plant integration Heaters number
P0301
Boiler plant present (0:NO; 1:YES)
P0302
Enable heaters during defrost (0:NO; 1:YES)
P0303
External probe is enabled for heaters regulation (0:NO; 1:YES)
P0304
Setpoint for the enable of heater in integration of plant
P0305
Differential for the enable of heater in integration of plant
P0306
External probe is enabled for boiler regulation (0:NO; 1:YES)
P0307
Setpoint for the enable of boiler in integration of plant
P0308
Differential for the enable of boler in integration of plant
P0309
Heaters band=reg.band x
P0310
Enable heaters plant during coil antifreeze (0:NO; 1:YES)
P0311
Set for stop compressors for external low temperature
P0312
Differential for stop compressors for external low temperature
P0314
Enable Analogic input B7 (0:NO; 1:YES)
P0315
Enable Analogic input B6 (0: NO; 1: YES)
P0316
Differential to start boiler
2.4.5
MENÙ 04
Num Par
Description
P0401
Multi unit control unit number
P0402
Cascade type (0: ONE UNIT FOR DHW; 1: ALL UNIT FOR DHW; 2: EXCHANGER FOR DHW)
P0403
Insertion delay
P0404
Disinsertion delay
2.4.6
MENÙ 05
Num Par
Description
P0506
Type of regulation compressors heating (0: P; 1: P+I)
P0507
Differential activations compressor heating
P0508
Integral Time regulation compressors heating
P0509
Type of regulation compressors cooling (Proportional or Prop-Interg)
P0510
Differential activations compressor cooling
P0511
Integral Time regulation compressors cooling
P0512
Type of regulation compressors DHW (Proportional or Prop-Interg)
P0513
Differential DHW for regulation
P0514
Integral Time regulation compressors DHW
P0515
Set for stop compressors for external high temperature
P0516
Differential for stop compressors for external high temperature
P0521
Night limit differential - Summer
P0522
Night limit offset - Summer
P0522
Night limit differential - Winter
P0523
Night limit offset - Winter
P0524
Night limit - Maximum compressor speed during limitation
P0525
Night limit - Maximum fan speed during limitation
P0526
Set for stop compressors for external high temperature in Summer
MEHITS S.p.A.
TECHNICAL MANUAL
Default
0
0
0
1
-5.0
2.0
1
-5.0
2.0
1.0
0
-20.0
2.0
0
0
4.0
Default
1
1
1
1
Default
1
8.0
150
1
6.0
150
1
4.0
150
45.0
2.0
99.0
1.0
1.0
1.0
50.0
0.0
45.0
19
Version NC05 - Translation of the Original Instructions
Unit
Min.
Max.
-
0
2
-
0
1
-
0
1
-
0
1
°C
-999.9
999.9
°C
-99.9
99.9
-
0
1
°C
-999.9
999.9
°C
-99.9
99.9
°C
0
99.9
-
0
1
°C
P133Z
999.9
°C
-99.9
99.9
-
0
1
-
0
1
°C
0
99.9
Unit
Min.
Max.
-
1
4
-
0
2
min
0
99
min
0
99
Unit
Min.
Max.
-
0
1
°C
0.5
15.0
s
1
999
-
0
1
°C
0.5
15.0
s
1
999
-
0
1
°C
0.5
15.0
s
1
999
°C
-999.9
999.9
°C
-99.9
99.9
°C
0
99.9
°C
0
99.9
°C
0
99.9
°C
0
99.9
%
50.0
100.0
%
0
100.0
°C
-999.9
999.9