Menù 02 - Mitsubishi Electric i-BX-N Technical Manual

Table of Contents

Advertisement

TM_i-BX(-N)_NC05_00_06_20_EN
Num Par
Description
P019D
Configuration of digital input 9 (0: LOW ENERGY FARE; 1: BACKUP BOILER)
P019E
Logic of summer/winter output (0: NORMALLY OPEN; 1: NORMALLY CLOSED)
P019F
Configuration NO4 pCOe n.1 (0: ZONE HT1; 1: SUMMER/WINTER)
2.4.3
MENÙ 02
Num Par
Description
P0200
Type of recirculation DHW (0: by DIN; 1: scheduler DHW)
P0201
Time DHW recirculation
P0202
Type of configuration DHW (0: Disabled; 1: Heat pump only; 2: Heaters only; 3: Heat pump +
Heaters)
P0205
Enable modulating of the DHW pump (0:NO; 1:YES)
P0206
Setpoint pump DHW
P0207
Differential pump DHW
P0208
Enable overboost for DHW (0:NO; 1:YES)
P0209
Set overboost DHW
P0210
Differential Overboost
P0211
Antilegionella temperature setpoint
P0212
Fixed days or period for antilegionella (0: Enabled fixed days; 1: Enabled period)
P0213
Enable the antilegionella cycle on Monday (0:NO; 1:YES)
P0214
Enable the antilegionella cycle on Tuesday (0:NO; 1:YES)
P0215
Enable the antilegionella cycle on Wednesday (0:NO; 1:YES)
P0216
Enable the antilegionella cycle on Thursday (0:NO; 1:YES)
P0217
Period for antilegionella cycle
P0218
Enable the antilegionella cycle on Friday (0:NO; 1:YES)
P0219
Enable the antilegionella cycle on Saturday (0:NO; 1:YES)
P0220
Enable the antilegionella cycle on Sunday (0:NO; 1:YES)
P0221
Hour start antilegionella cycle
P0222
Enable antilegionella (0:NO; 1:YES)
P0223
Antilegionella type (0: ONLY HEAT PUMP; 1: ONLY HEATERS; 2: HEATERS+HEAT PUMP)
P0224
Threshold for alarm no antilegionella
P0225
Maximum time for antilegionella cycle
P0226
Min time unit work for plant
P0227
Max time unit work for DHW
P0228
Enable antifreeze DHW (0:NO; 1:YES)
P0229
Setpoint antifreeze DHW
P0230
Differential antifreeze DHW
P0231
Time of change status of 3way valve
P0232
Enable Analogic input B3 (0:NO; 1:YES)
P0233
Enable DHW sniffer (0:NO; 1:YES)
P0234
Substitution temperature with heaters
MEHITS S.p.A.
TECHNICAL MANUAL
Default
0
0
0
Default
0
5
0
0
30.0
10.0
1
60.0
5.0
65.0
0
1
0
0
0
1
0
0
0
2
0
0
2
180
20
60
1
5.0
3.0
12
0
0
-20.0
18
Version NC05 - Translation of the Original Instructions
Unit
Min.
Max.
-
0
1
-
0
1
-
0
1
Unit
Min.
Max.
-
0
1
min
0
99
-
0
3
-
0
1
°C
-999.9
999.9
°C
0.0
99.9
-
0
1
°C
0.0
999.9
°C
0.0
99.9
°C
-99.9
99.9
-
0
1
-
0
1
-
0
1
-
0
1
-
0
1
d
1
30
-
0
1
-
0
1
-
0
1
h
0
23
-
0
1
-
0
2
d
0
23
min
1
500
min
0
500
min
0
500
-
0
1
°C
0
999.9
°C
0
999.9
0
99.9
-
0
1
-
0
1
°C
-20.0
20.0