Installation Checklist - Hussmann TY3ECRC Installation & Operation Manual

End/island caseextended canopyround cornerself-contained
Table of Contents

Advertisement

Date:
Store:
Case Model#
Cond. Unit Model# Serial#
Cases Check / Initial
Prior to beginning review the installation manual on moving, lifting, and setting the case
Report any damage to Hussmann Account Manager or Sales representative right away
Shipping pins, boards, clips, tape removed and disposed of
Intake must be facing away from store entrance doors
Height clearance measured from the floor must be minimum 10 ft vertically
Minimum of 36 in. clearance between case intake/discharge if near an open aisle for proper airflow
8 feet of clearance must be maintained from a solid wall for Intake/Discharge of condensing unit
Case must be located minimum 15 ft away from entry doors
If case is located near windows and direct sunlight is present, the windows are tinted or shaded
Case set location has been reviewed for artificial airflows that can disrupt the case air curtain, entry door air
curtains, HVAC registers etc.
Cases must be level/plum for proper draining of condensate
Plumbing Check / Initial
Case condensate Floor sink
There are no water leaks from the case
Refrigeration Check / Initial
This case application refrigerant is
Leak check all valves, connections, lines with electronic leak detector and soap
Verified that there are no refrigerant leaks, and that any detected leaks have been repaired
The defrost schedule has been reviewed in the installation manual and the systems has been set accordingly
Defrost frequency per day
Allow the case to run and cycle on factory setpoint for 4 hours.
Check store conditions after unit has stabilized. Unit is manufactured to operate in 80F 55 RH max. Adjust
store conditions accordingly.
Case Setpoint _____ adjust accordingly based on store conditions.
Case Discharge temp
Case TXV Superheat setting
This checklist is a supplement to the provided installation manual and should be completed to ensure that all installation procedures were
completed and verify normal case operation at startup. Hussmann Tech Support 866-785-8499
HUSSMANN ENTYCE ISLAND INSTALLATION CHECKLIST
Electric Evap pan
Defrost Off time
30° to 34°
6° to 8°
Tech Name:
Serial#
Condensate pump
448A
( Self Contained)
Defrost Termination Temp
(Should be < 10 Degrees)
5
See the following sheet to continue...