Customer Unit Configuration; Water Reversing Valve; R/W Psw W - Daikin EWWQ-KC Operating Manual

Water to water heat pump units with scroll compressors
Table of Contents

Advertisement

The path in the Web HMI interface for Master/Slave configuration is "
". Please refer to specific documentation for more information about of this topic.
Master/Slave

3.16. Customer Unit Configuration

Except for factory configurations, the client can custom the unit depending on his needs and options acquired. The allowed
modifications regard Unit Boost, Fan Boost, IO Ext Module, HMI Type, Pump Ctrl Type, SCM Address,
External Alarm, Costant Heating Capacity, SCM Number OF Units, Fan Silent Speed, Domestic Hot
Water.
All these customer configurations for the unit can be set in page [15].
Page
Parameter
15
00
(Evaporator Pump Ctrl Mode)
01
(Evap Control Measure)
02
(Evap Control Device)
03
(EWT Sensor Enable)
04
(Condenser Pump Ctrl Mode)
05
(Cond Control Measure)
06
(Cond Control Device)
07
(SCM Address)
08
(External Alarm)
09
(Number of Units)
10
(Water
Behaviour)
11
(Water
Reversing
Delay)
12
(Water
Reversing
Delay)
13
(Evap Nominal DT)
14
(Cond Nominal DT)
15
(HMI Sel)
The path in the Web HMI interface for Customer Configuration settings is "

3.17. Water Reversing Valve

The Water Reversing Valve(WRV), depending on the model (NC/NO), goes to exchange externally to the chiller the hot water
with the cold water or the other way around. to control the correct functioning of the valve it has been given the possibility to give
a delay to the opening in the passage between cold and hot water and the other way around.
Page
Parameter
11
15
(Water Reversing Valve Behaviour)
12
(Water
Reversing
Delay)
D-EOMHP01501-22_00EN 20/29
[16.13] Interval Time
[16.14] Switch Time
[16.15] Temp Compensation
[16.16] Tmp Cmp Time
[16.17] M/S Alarm Code
Range
0-3
0-2
0-2
0-1
0-3
0-2
0-2
0-4
0-3
0-2
0-1
Reversing
Valve
0-120
Valve
To
Cool
0-120
Valve
To
Heat
0-10
0-10
0-1
Range
0-1
0-120
Valve
To
Cool
1-365
1-24
Off-On
0-600 minutes
0..511
Main Menu
Commission Unit
Description
0 =On-Off Mode
1 = Fixed Speed
3 = DeltaT Mode
0=No
1=EvapIn
2=EvapOut
0=No
1=Valve
2=VFP
0=Sensor not connected
1=Sensor Connected
0 =On-Off Mode
1 = Fixed Speed
3 = DeltaT Mode
0=No
1=CondIn
2=CondOut
0=No
1=Valve
2=VFP
0 = Standalone
1 = Master
2 = Slave1
3 = Slave2
4 = Slave3
0 = No
1 = Event
2 = Rapid Stop
0 = 2 Units
1 = 3 Units
2 = 4 Units
0=Normally Close
1=Normally Open
0-120s
0-120s
0-10
0-10
0=Evco
1=Siemens
Main Menu
Commission Unit
Description
0=Normally Close
1=Normally Open
0-120s
W
1
W
1
W
1
W
1
R
1
Configuration
R/W
Psw
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
W
1
"
Options
R/W
Psw
W
1
W
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ewlq-kc

Table of Contents