External Alarm; Thermostatic Source Control; Entering Water Temperature Control; Menu Parameter 09 - Daikin EWWQ-KC Operating Manual

Water to water heat pump units with scroll compressors
Table of Contents

Advertisement

02
(Stage Up DT)
03
(Stage Down DT)
04
(Stage Up Delay)
05
(Stage Down Delay)
06
(Evaporator Freeze)
07
(Condenser Freeze)
08
(Low Pressure Unload)
The path in the Web HMI interface is "Main Menu → View/Set Unit → Thermostatic Control".
3.9.

External Alarm

The External Alarm is a digital contact that can be used to communicate to the UC an abnormal condition, coming from an external
device connected to the unit. This contact is located in the customer terminal box and depending on the configuration can causes
a simple event in the alarm log or also the unit stop. The alarm logic associated to the contact is the following:
Contact state
Alarm State
Opened
Alarm
Closed
No Alarm
The configuration is performed from Page [15] as shown below:
Menu
Parameter
15
09
(
Ext Alarm
)
The web HMI path for the External Alarm configuration is:

3.9.1. Thermostatic Source Control

The unit allows water control based on entering water temperature or leaving water temperature.
Thermostatic Control Parameters (Page 9) must be set according to customer requirements in order to fit as much as possible
the Water Plant conditions.
Thermostatic Control can be set into:
EWT Control (Selectable only if EWT Sensor are enabled (15.03→1)
LWT Control (Default)
3.9.1.1.

Entering Water Temperature Control

In EWT Control, compressor starts/stops depend on Entering Water Temperature value, with respect to the thermostatic control
parameters.
Parameter
Control Temperature
SP

Startup DT

Shutdown DT

Nominal DT
D-EOMHP01501-22_00EN 14/29
0-5
Delta temperature respect the active setpoint to start second
compressor
0-MIN(5, 60-LwtSp)
Delta temperature respect the active setpoint second
compressor
1÷60 [min]
Minimum time between the compressor startup
0÷30 [min]
Minimum time between the compressor shutdown
if Unit mode = 1 or 3
Defines the minimum water temperature before the unit alarm
-18 ÷ 6 [°C]
for evaporator freezing in triggered
if Unit mode = 0 or 2
+2 ÷ 6 [°C]
if Unit mode = 1 or 3
Defines the minimum water temperature before the unit alarm
-18 ÷ 6 [°C]
for condenser freezing in triggered
if Unit mode = 0 or 2
+2 ÷ 6 [°C]
if Unit mode = 1 or 3
Minimum pressure before compressor starts unload action in
150÷800 [kPa]
order to increase evaporating pressure
if Unit mode = 0 or 2
600÷800 [kPa]
The alarm is generated if the contact remains opened for at least 5 seconds
The alarm is reset just the contact is closed
Range
Description
0 = No
External Alarm disabled
1 = Event
Event configuration generates an alarm in the controller but takes
the unit running
2 = Rapid Stop
Rapid Stop configuration generates an alarm in the controller and
performs a rapid stop of the unit
Commissioning
Description/Value
Entering Water Temperature
Based on Entering Water Temperature
2.7 dK (default value as described in previous chapter)
1.7 dK (default value as described in previous chapter)
Depends on Unit Mode, set it in 15.14, 15.15 parameters (Nominal Evap DT, Nominal Cond DT)
Note
Configuration
Options
W
1
W
1
W
1
W
1
W
2