Controller Ip Setup; Daikin On Site - Daikin EWWQ-KC Operating Manual

Water to water heat pump units with scroll compressors
Table of Contents

Advertisement

Menu
Parameter
18
01
(Max Reset)
02
(Start Reset DT)

3.12. Controller IP Setup

The Controller IP Setup can be accessed from menu [13] where is possible to choose between the static or dynamic IP and
manually set IP and network Mask.
Menu Parameter
Sub-Parameter Description
13
00
N/A
(DHCP)
01
N/A
(IP)
02
N/A
(Mask)
03
00 IP#1
(Manual IP)
01 IP#2
02 IP#3
03 IP#4
04
00 Msk#1
(Manual Mask)
01 Msk#2
02 Msk#3
03 Msk#4
In order to modify the MTIV IP Network configuration, do the following operations:
access the
Settings
set the DHCP option to Off
modify the IP, Mask, Gateway, PrimDNS and ScndDNS addresses, if needed, taking care of the current network
settings
set
Apply changes
The default internet configuration is:
Note that if the DHCP is set to On and the MTIV internet configurations shows the following parameter values then an internet
connection problem has occurred (probably due to a physical problem, like the Ethernet cable breaking).

3.13. Daikin On Site

Daikin on site connection can be enabled and monitored through menu [12]:
Menu
Parameter
Range
12
00
Off = Connection Off
(Enable)
On = Connection On
01
0-6 = Not connected
(State)
7 = Connected
D-EOMHP01501-22_00EN 18/29
Range
Description
0..10 [°C]
Max Reset setpoint. It represents the maximum temperature variation that the
selection of the Setpoint Reset logic can cause on the LWT.
It represents the "threshold temperature" of the DT to activate the LWT setpoint
0..10 [°C]
reset, i.e. the LWT setpoint is overwritten only if the DT reaches/overpasses the
SRΔT.
Off = DHCP Off
The DHCP option is disabled.
On = DHCP On
The DHCP option is enabled.
"xxx.xxx.xxx.xxx"
Represent the current IP address. Once entered [13.01] parameter, the HMI will
automatically switch between all four IP-Address fields.
"xxx.xxx.xxx.xxx"
Represent the current Subnet Mask address. Once entered [13.02] parameter, the HMI
will automatically switch between all four Mask fields.
Defines the first field of IP-Address
Defines the second field of IP-Address
Defines the third field of IP-Address
Defines the fourth field of IP-Address
Defines the first field of Mask
Defines the second field of Mask
Defines the third field of Mask
Defines the fourth field of Mask
menu
parameter to
to save the configuration and restart the MTIV controller.
Yes
Parameter
IP
Mask
Gateway
PrimDNS
ScndDNS
Parameter
IP
Mask
Gateway
PrimDNS
ScndDNS
Default Value
192.168.1.42
255.255.255.0
192.168.1.1
0.0.0.0
0.0.0.0
Value
169.254.252.246
255.255.0.0
0.0.0.0
0.0.0.0
0.0.0.0
Description
DoS connection is disabled
DoS connection is enabled
DoS actual connection state
R/W
W
W
R/W
W
R
R
W
W
W
W
W
W
W
W
R/W
Psw
W
1
R
1