A - Jumper
B - Cut here
6

Related Drive Parameters

These parameters set the drive for operation with the option. Make sure that the parameter settings in this table are
correct before you start network communications.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
(For Drive)
b1-02
Run Command Selection 1
(0181)
(For Drive, D1000)
b1-18
Voltage Reference Source
(0179)
(For D1000)
F6-01
Communication Error
Selection
(03A2)
(For Drive)
YASKAWA SIEP C730600 83E CC-Link Technical Manual
Figure 5.20 Termination Resistor
Figure 5.21 Termination Resistor Wiring
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : MEMOBUS/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
• Set b1-02 = 3 [Run Command Selection 1 = Option PCB] to use the master device and
serial communications to start and stop the drive. Set b1-01 = 3 to use the master device to
control the frequency reference of the drive.
• The default setting is different for different drives. Refer to the instruction manual of your
specific drive for more information.
Selects the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : MEMOBUS/Modbus Communications
3 : Option PCB
Note:
Set b1-02 = 3 to start and stop the drive with the master device using serial communications.
Set b1-01 = 3 [Frequency Reference Selection 1 = Option PCB] to use the master device to
control the frequency reference of the drive.
Selects the voltage reference input source.
0 : Keypad - RUN and STOP keys
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option
7 : Input Voltage Based Control 1
8 : Input Voltage Based Control 2
Note:
• On D1000, to use the CC-Link master device as the voltage reference, set b1-18 = 3.
Selects drive response when the drive detects a bUS [Option Communication Error] error during
communications with the option.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm - Run at d1-04
C - Cut (removes approximately 5.5 mm (0.21 in) of
the covering at the tip.)
Description
6 Related Drive Parameters
Default
(Range)
1
(0 - 4)
1
(0 - 3)
8
(0 - 3, 7, 8)
1
(0 - 5)
23