Trane GAF2A0A36S3AEC Installer's Manual page 32

50 hz convertible air handlers 3 – 5 ton
Table of Contents

Advertisement

STEP 3 - Route conduit (if used) to the entry point
and connect.
1.
Use one hand to secure the conduit nut from inside of
the heater compartment.
2.
Connect field supplied conduit to conduit nut. GAM2
models will use up to 1-1/2" conduit and GAF2 mod-
els will use up to 3/4" conduit.
Note: Reducing bushings may be required for your
application.
STEP 4 - If an electric heater IS NOT being
installed, remove the pigtail harness from the
documentation pack and connect it to the plug
on the inside of the Heater Compartment in the
cabinet.
If an electric heater IS being installed, see
the Installer's Guide shipped with the electric
heater.
Connect L1, L2, and ground wiring to pigtail
harness in Heater Compartment using wire
nuts. The incoming ground wiring will mate up
with the green wire shown in the illustration.
STEP 5 - If the L1, L2, and ground wires enter
the case from the left side (GAM2 only), use a
field supplied 1/2"-5/8" maximum length screw
and wire tie to hold the wires to the top center
of the Heater Compartment.
32
BLACK
RED
GREEN - GROUND