Installation
NON-HAZARDOUS
LOCATION ONLY
ISO
Tempered
Water
Unit
POLY
Tempered
Water
Unit
Robot
Control
Cabinet
Main Control
Panel
460 VAC Supply Voltage
NOTES:
1. All intrinsically safe conduits/wires/cables are to enter the main control panel on the safety barrier side of the main control panel. This wiring
must not come near or in contact with any non-intrinsically safe wiring.
2. Any replacement of intrinsically safe barriers must be an identical replacement to maintain intrinsically safe circuit rating.
3. The non-intrinsically safe terminals (power rail) must not be connected to any device which uses or generates more than 250 Vrms or d.c.
unless it has been determined that the voltage has been adequately isolated.
4. The installation must meet the requirements of the National Electric Code, NFPA 70, Article 504 Resp., Article 505 and ANSI/ISA 12.06.01
5. Multiple earthing of components is allowed only if high integrity equipotential system is realized between the points of bonding.
6. Do not operate system with safety barrier cover removed.
WARNING: Substitution of components may impair intrinsic safety. For installation, maintenance or operation instructions, see instruction
manual.
F
. 4: Intrinsically Safe Installation
IG
12
X-P
SO
X-P
SO
Safety
X-P
Barrier
SO
Intrinsically
Safe Wiring
through
Barriers
HAZARDOUS (CLASSIFIED) LOCATION
CLASS I, DIV I, GROUP D
ISO
Agitator
X-P
SO
X-P
SO
ISO
Metering
Pump
Machine
Frame
Panel
All conduits must be rigid metal conduit
X-P SO = Explosion Proof Seal-Off
Robot
Base
ISO
POLY
Agitator
Heater
X-P
X-P
SO
SO
X-P
X-P
SO
SO
POLY
ISO
Metering
Heater
Pump
313813A