H3DE
J BASIC OPERATION
Selector Setting
The selectors can be turned clockwise and counterclockwise to
select the desired time unit, time scale, or operating mode.
Each selector has a snap mechanism that secures the selector at
a given position. Set the selector at a position at which it is
secured. Do not set it midway between two securing positions or
a malfunction could result from improper setting.
Operating mode selector

Operating Mode Selection

The H3DE-M/-S can be set to any one of the operating modes A
to J. Turn the operating mode selector with a screwdriver until the
desired operating mode (A, B, B2, C, D, E, G, or J for the
H3DE-M and A, B2, E, or J for the H3DE-S) appears in the
operating mode display window located below the selector.
J TIMING CHART
Note: 1. The minimum power reset time is 0.1 s and the minimum signal input time is 0.05 s.
2. The letter "t" in the timing charts stands for the set time and "t- -a" means that the period is less than the time set.
Operating
Timing chart
mode
A: ON-delay
Power (A
and A
1
Start (B
and A
1
2
(See Note.)
Output relay: NC
15 and 16
(25 and 26)
Output relay: NO
(output indicator)
15 and 18
(25 and 28)
Power indicator
Groove for
screwdriver
A
Operating mode
display window
t
t- -a
)
2
)
(This table continues on the next page.)
Time Unit and Time Scale Selection
The desired time unit (sec, min, hrs, or 10h) can be displayed in
the time unit display window above the time setting dial by
turning the time unit selector located at the upper right corner of
the front panel. The time scale (0.1 or 1) is selected with the time
scale selector at the upper left corner of the front panel. It
appears in the scale range display window above the selector.
Time unit display window
Scale range display
window
Scale range
selector
Time unit selector
t
Basic operation
Power
*
Start
Output
*
For power-on operation, impose voltage to the
Start input. The Timer starts operating at the
moment the power is turned on.
** Start input is invalid while the Timer is in opera-
tion.