Programming the Symbio 800 AdaptiView

Note: For more information regarding the use of the
Tracer TU service tool, installation, operation and
programming of the Symbio 800 controller,
operation of the control system, and a guide to the
diagnostics and troubleshooting of the control
system, please refer to the following manuals (or
their most recent versions):
BAS-SVU047*-EN, Getting Started Guide: TU Service
Tool
CTV-SVP004*-EN, Tracer TU Service Tool for Water-
Cooled CenTraVac Chillers with Symbio Control
CVHE-SVX005*-EN, Installation, Operation, and
Maintenance - CVHE, CVHF, and CVHG Water-Cooled
CenTraVac™ Chillers With Symbio Control
CVRF-SVP01*-EN, Programming Guide: Tracer
Symbio Panel Upgrade
CTV-SVU004*-EN, Operations Guide - Tracer®
AdaptiView™Display for CenTraVac™Water-Cooled
Chillers with Symbio
CTV-SVD005*-EN, Diagnostics Manual - Diagnostic
Descriptions, Troubleshooting Tables, and Control
Component Overview for Water-Cooled CenTraVac™
Chillers with Tracer AdaptiView™ Control
Figure 41. Application software download
CDUB-SVN002B-EN
NOTICE
Separate AC Power Required for
Computers when Working on Symbio
800!
When doing any service work on a Tracer AdaptiView
control system that requires connecting a laptop
computer running Tracer TU service tool software to
the Symbio 800 controller, the laptop must be
operated from a SEPARATE AC power source AT ALL
TIMES. NEVER run the laptop on internal battery
power alone while connected to a Symbio 800
controller! Should the computer's internal battery die
or malfunction while connected to a Symbio 800, fatal
corruptions could occur to the electronic files within
the controller that will render it completely inoperable
and unable to accept new programming, requiring it to
be replaced with new Symbio 800. Damaging a Symbio
800 controller in this manner is not covered under any
warranty!
1. Obtain a working AC power adaptor with which to
power the technician's laptop.
2. Connect the computer with the Tracer TU service tool
software to the service port of the Tracer Symbio 800
controller with a USB type A/B cable.
3. Open Tracer TU.
Note: Tracer TU not scheduled to have feature used in
Step 5
before August 2022. If not available, the
unit parameters will need to be manually
loaded from saved chiller service report.
4. Upgrade controller firmware as follows:
a. In the Utilities menu, select File Transfer Utility.
b. In the File Transfer dialog box, select Symbio 800
controller, and click Next.
c. Browse to the firmware file and click Next.
d. Click Start.
e. When upgrade is complete, click Finish.