Upgrading Display Firmware - Trane Symbio 800 Installation Instructions Manual

Control upgrade kit for uc800 adaptiview display
Table of Contents

Advertisement

Installation

Upgrading Display Firmware

Important:
This firmware upgrade applies to existing,
reused black frame AdaptiView displays.
Gray frame displays are incompatible with
Symbio and must be replace with the new
black frame display.
Display firmware download must be done
using a functional UC800 controller. If the
existing UC800 controller is not functional,
a substitute UC800 controller must be
obtained.
Download CANNOT be done with a Symbio
controller. Use of a Symbio controller will
result in a loss of communication to the
UC800, which cannot be restored.
Figure 4.
Tracer AdaptiView selection
7. In the next dialog box, click the "Browse" button and
navigate to the display firmware file, then click "Open"
to select the file and then click "Next".
Notes:
Obtain TD display firmware from the Trane
Commercial Downloads page, Symbio™ 800
section.
Recommended firmware location:
C:\ProgramData\Trane\Tracer TU\Firmware\TD12
10
Upgrade the display firmware by completing the following
steps.
1. Connect your laptop to the USB port on the UC800 or
on the control panel.
2. Start Tracer® TU.
3. Click the "Utilities" on top of TU and click "File Transfer
Utility".
4. Click "Yes" for the save file popup.
5. The File Transfer dialog box will appear. Deselect the
UC800 (uncheck the box) and select the Tracer
AdaptiView (check the box).
6. Click "Next".
CDUB-SVN002B-EN