Section 4: Specifications; Environmental Specifications; Physical Specifications; Performance Specifications - Generac Power Systems PWRmanager Owner's Manual

12 relay load controller
Table of Contents

Advertisement

Section 4: Specifications

Environmental Specifications

Description
Mounting Options
Operating Temperature Range
IP Rating

Physical Specifications

Description
Dimensions (excluding flange)
Weight
Wire Sizes

Performance Specifications

Description
Per-circuit Current Capacity
Number of Controllable Relays
Number of HVAC-control Relays (no metering)
Power Consumption
Maximum Total Current
Warranty

Connectivity, Security

Description
WiFi Frequency Band
IP Addressing
Encryption

Compliance

Description
UL
Owner's Manual for Generac PWRmanager 12 Relay Load Controller
Value
Indoor, Outdoor, Flush Mount, and Surface Wall
Mount.
-40°F to 122°F (-40°C to 50°C)
3R Outdoor Mounting
Value
Width 14 in x Height 9 in x Depth 5 in
(35.56 cm x 22.86 cm x 12.7 cm)
14.3 lb (6.5 kg)
14 through 6 AWG
Value
60 A resistive 120 / 240 VAC
2 HP motor load 120 VAC
4 HP motor load 240 VAC
12
2
<20 W
450 A
10 years
Value
2.4 GHz
DHCP, Static
TLSv1.2
Value
UL916
Specifications
11

Advertisement

Table of Contents
loading

Table of Contents