Installation
Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the munic-
ipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble LED will
turn on to indicate the Disconnect condition.
2.7.3 ANN-SEC Option Card
The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.
1.
Remove the chassis mounting screw to the right of TB3 and replace it with the supplied 0.5" x 4-40 male-female standoff.
2.
Install the header into J13 on the main circuit board.
3.
Secure the ANN-SEC to the circuit board with the supplied screw.
FACP Circuit Board
32
Note: the 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal.
For an application of reverse polarity of a supervisory signal, refer to the Appendix titled "FACP with
Keltron" on page 114.
TBL Jumper
Disconnect
Switch
shown in
disconnect
position
Connect to FACP Connectors J4 & J5
Figure 2.17 4XTMF Transmitter Module
connector to J13 on
main circuit board
Figure 2.18 Installing the ANN-SEC Option Card
Polarities are shown for module activation
}
1+
Remote Alarm - Class 2
2-
3+
}
4-
Remote Trouble - Class 2
5
6+
7-
No connection
* Wiring from these terminals
can exit the protected premises.
Dummy load terminals 6 and 7
(4.7KΩ, ¼ watt resistor) if
Municipal Box is not connected.
Disconnect LED
J1
ANN-SEC
TB1
standoff and screw
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Installation of Optional Modules
(power-limited)*
(power-limited)*