v The overcurrent protective device or circuit breaker must be accessible to service
personnel to prevent the power from being turned on by someone other than
technician servicing the BladeCenter HT unit.
v The BladeCenter HT unit has a dc wire rating of 4 AWG (circular mil area of
33100-52600) and rated 90 degree C.
Note: The actual wire gauge and ring terminal will be determined by the current
draw and the length of wire run or as specified by the customer premises
guidelines.
v Flexible dc wiring is recommended to allow for minimum bend radius.
v The supply wiring to the power connectors must be terminated in UL recognized
insulated ring terminals, sized for a M6 stud, 4 AWG wire (circular mil area of
33100-52600) and a wire insulation diameter of 12.8 to 13.1 mm. An example of
this type of ring terminal is Amp Plasti-Grip type 52043–1 using Tyco Electronics
Hydraulic Crimping Tool part number 1490749–1.