Automatic Alarms - What to do

Before any automatic alarms have been sounded the
panel only operates in display mode (quiescent state).
The user must then turn the keyswitch to the right or enter
a Level 2 access code to enable the panel's pushbuttons.
Only one alarm condition can be displayed at a time
on the LCD. If fire alarms, faults and/or warning conditions
(Plant Alarm) are present on the panel at the same time,
they are displayed in the following priority order:
a. Fire Alarms.
b. Pre-alarms
c. Faults.
d. Warnings.
The alarm condition is registered in a log.
The user must then enter a Level 2 access code, or turn
the keyswitch to the right, to enable the panel's
pushbuttons. When the Level 2 access code is active,
the '
/
' buttons can be used to scroll through the
2
8
alarms and the '

3.1 Fire

Automatic panel actions:
If the system detects a fire alarm, the panel always does
the following automatically:
a. Operates the internal (high-pitched) buzzer.
b. Illuminates the red FIRE LEDs, and the numbered
red ZONE FIRE LED.
c. Displays information on the LCD regarding the fire
condition. The information includes device address
and device location (see example below).
LOGGED
DISPLAYED
ALARM
ALARM
CONDITION
CONDITIONS
FIRE
02 / 05
Z01
MAIN BUILDING
ZONE TEXT
DEVICE
ADDRESS
Note: If a delay is configured DELAYED is displayed on
the top line of the LCD. When a delay is active the
DELAY ACTIVE LED illuminates and the remaining
time before the first day mode delay expires is
displayed every 5 secs. The LED only extinguishes
when the delay period has expired.
d. Operates the sounders and output modules according
to the panel's Control-by-Event (CBE) Rules
(configured during the Commissioning stage).
5
' button will display the first alarm.