To Perform A Test Run; To Perform An Actuator Test Run; Underfloor Heating Screed Dryout - Daikin Altherma EDLQ011-016CW1 Installer's Reference Manual

Low temperature monobloc
Hide thumbs Also See for Altherma EDLQ011-016CW1:
Table of Contents

Advertisement

1 Set the user permission level to Installer. See
permission level to Installer" on
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Automatic and press
4 Go to [A.7.3.4]
> Installer settings > Commissioning > Air
purge > Start air purge and press
function.
Result: Air purging will start and the following screen will be
shown.
Tue
Air purge
Flow rate
0.5
l/min
Speed
Low
Circuit
SHC
Stop
Adjust
Scroll
INFORMATION
If the temperature of the water circuit is low, and glycol was
added to it, then the flow rate will NOT be displayed.
To interrupt air purge
1 Press
and press
to confirm the interruption of the air
purge function.
9.4.3

To perform a test run

Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Go to [A.7.1]:
> Installer settings > Commissioning > Test
run.
3 Select a test and press
. Example: Heating.
4 Select OK and press
.
Result: The test run starts. It stops automatically when done
(±30 min). To stop it manually, press
INFORMATION
When starting up the system in a cold climate, and NO
backup heater kit was installed, it may be required to start
up with a small water volume. To do this, gradually open
the heat emitters. As a result, the water temperature will
gradually rise. Monitor the inlet water temperature ([6.1.6]
in the menu structure) and make sure it does NOT drop
below 15°C.
INFORMATION
If 2 user interfaces are present, you can start a test run
from both user interfaces.
▪ The user interface used to start the test run displays a
status screen.
▪ The other user interface displays a "busy" screen. You
cannot use the user interface as long as the "busy"
screen is shown.
If the installation of the unit has been done correctly, the unit will
start up during test operation in the selected operation mode. During
the test mode, the correct operation of the unit can be checked by
monitoring leaving water temperature (heating/cooling mode) and
tank temperature (domestic hot water mode).
To monitor the temperature, go to [A.6] and select the information
you want to check.
EBLQ+EDLQ011~016CAV3+W1 + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
"To set the user
page 51.
> Installer settings >
.
to start the air purge
01:18
"To set the user
page 51.
, select OK and press
.
9.4.4

To perform an actuator test run

Purpose of the actuator test run is to confirm the operation of the
different actuators (e.g., when you select pump operation, a test run
of the pump will start).
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Make sure the room temperature control, the leaving water
temperature control and the domestic hot water control are
turned OFF via the user interface.
3 Go to [A.7.4]:
> Installer settings > Commissioning >
Actuator test run.
4 Select an actuator and press
5 Select OK and press
.
Result: The actuator test run starts. It automatically stops when
finished. To stop it manually, press
Possible actuator test runs
▪ Booster heater test
▪ Backup heater (step 1) test
▪ Backup heater (step 2) test
▪ Pump test
INFORMATION
Make sure that all air is purged before executing the test
run. Also avoid disturbances in the water circuit during the
test run.
▪ 2-way valve test
▪ 3-way valve test
▪ Bivalent signal test
▪ Alarm output test
▪ Cooling/heating signal test
▪ Quick heat-up test
▪ Circulation pump test
9.4.5

Underfloor heating screed dryout

This function is used for drying out the screed of an underfloor
heating system very slowly during the construction of a house. It
allows the installer to program and execute this program.
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are
turned OFF.
If a backup heater kit is part of the system, this function can be
executed without finishing the outdoor installation. In this case, the
backup heater will perform the screed dryout and supply the leaving
water without heat pump operation.
INFORMATION
▪ If Emergency is set to Manual ([A.6.C]=0), and the unit
is triggered to start emergency operation, the user
interface will ask confirmation before starting. The
underfloor heating screed dryout function is active even
if the user does NOT confirm emergency operation.
▪ During underfloor heating screed dryout, pump speed
limitation [9‑0D] is NOT applicable.
9 Commissioning
"To set the user
page 51.
. Example: Pump.
, select OK and press
.
Installer reference guide
79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents