To Connect The Interconnection Cable Between Option Box And Control Box; To Connect The Electrical Meters; To Connect The Alarm Output; To Connect The Space Cooling/Heating On/Off Output - Daikin Altherma EDLQ011-016CW1 Installer's Reference Manual

Low temperature monobloc
Hide thumbs Also See for Altherma EDLQ011-016CW1:
Table of Contents

Advertisement

7 Installation
X2M
A4P
A4P
X1M
X1M
1
2
3
1
X8M
1
GND
2
L
3
N
2 Fix the cable with cable ties to the cable tie mountings to
ensure strain relief and to make sure that it does NOT come in
contact with sharp edges.
CAUTION
Do NOT push or place redundant cable length in the unit.
7.8.14
To connect the interconnection cable
between option box and control box
1 Connect the connectors from the accessory bag to X5A on A1P
of both the control box and the option box PCB.
2 Connect the connectors by way of a field-supplied cable.
a
X5A
A4P
a
Connectors (accessory)
b
Interconnection cable (field supply)
7.8.15

To connect the electrical meters

INFORMATION
▪ Requires option box EK2CB07CAV3.
▪ To be connected to option box EK2CB07CAV3.
INFORMATION
In case of an electrical meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X2M/7 and X2M/9; the negative polarity to X2M/8 and
X2M/10.
1 Connect the electrical meters cable to the appropriate terminals
as shown in the illustration below.
Installer reference guide
46
X2M
2
3
X8M
b
a
X5A
A4P
X2M
A4P
10
9
8
7
X1M
X8M
S5P S6P
2 Fix the cable with cable ties to the cable tie mountings.
7.8.16

To connect the alarm output

INFORMATION
▪ Requires option box EK2CB07CAV3.
▪ To be connected to option box EK2CB07CAV3.
1 Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.
X2M
A4P
15
13
X1M
X8M
2 Fix the cable with cable ties to the cable tie mountings.
7.8.17
To connect the space cooling/heating ON/
OFF output
INFORMATION
▪ Requires option box EK2CB07CAV3.
▪ To be connected to option box EK2CB07CAV3.
1 Connect the space cooling/heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.
EBLQ+EDLQ011~016CAV3+W1 + EK(2)CB07CAV3 +
Daikin Altherma low temperature monobloc
EKMBUHCA3V3+9W1
4P522034-1 – 2018.01