Daikin Altherma EDLQ011-016CW1 Installer's Reference Manual page 104

Low temperature monobloc
Hide thumbs Also See for Altherma EDLQ011-016CW1:
Table of Contents

Advertisement

6/9
Field settings table
Breadcrumb
Field code
Setting name
A.8
[4-00]
What is the BUH operation mode?
A.8
[4-01]
Which electric heater has priority?
A.8
[4-02]
Below which outdoor temperature is heating allowed?
A.8
[4-03]
Operation permission of the booster heater
A.8
[4-04]
How to protect the water pipes from freezing
A.8
[4-05]
--
A.8
[4-06]
-- (Do not change this value)
A.8
[4-07]
Enable the second step of the backup heater?
A.8
[4-08]
--
A.8
[4-09]
--
A.8
[4-0A]
--
A.8
[4-0B]
Automatic cooling/heating changeover hysteresis.
A.8
[4-0D]
Automatic cooling/heating changeover offset.
A.8
[4-0E]
Is the installer on site?
A.8
[5-00]
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
A.8
[5-01]
What is the equilibrium temperature for the building?
A.8
[5-02]
Space heating priority.
A.8
[5-03]
Space heating priority temperature.
A.8
[5-04]
Set point correction for domestic hot water temperature
A.8
[5-05]
--
A.8
[5-06]
--
A.8
[5-07]
--
A.8
[5-08]
--
A.8
[5-09]
--
A.8
[5-0A]
--
A.8
[5-0B]
--
A.8
[5-0C]
--
A.8
[5-0D]
What type of backup heater installation is used?
A.8
[5-0E]
--
A.8
[6-00]
The temperature difference determining the heat pump ON temperature.
A.8
[6-01]
The temperature difference determining the heat pump OFF temperature.
A.8
[6-02]
What is the capacity of the booster heater?
A.8
[6-03]
What is the capacity of the backup heater step 1?
A.8
[6-04]
What is the capacity of the backup heater step 2?
A.8
[6-05]
--
A.8
[6-06]
--
A.8
[6-07]
--
A.8
[6-08]
What is the hysteresis to be used in reheat mode
A.8
[6-09]
--
A.8
[6-0A]
What is the desired comfort storage temperature?
A.8
[6-0B]
What is the desired eco storage temperature?
A.8
[6-0C]
What is the desired reheat temperature?
A.8
[6-0D]
What is the desired DHW production type?
A.8
[6-0E]
What is the maximum temperature set point?
A.8
[7-00]
Domestic hot water booster heater overshoot temperature
A.8
[7-01]
Domestic hot water booster heater hysteresis
A.8
[7-02]
How many leaving water temperature zones are there?
A.8
[7-03]
--
A.8
[7-04]
--
A.8
[7-05]
Boiler efficiency
A.8
[8-00]
--
4P522033-1 - 2018.01
Range, step
Default value
R/W
0~2
0: Disabled
1: Enabled
R/W
0~2
0: None
1: BSH
2: BUH
R/W
14~35°C, step: 1°C
35°C
R/W
0: Limited
1: No limit
2: Most optimum
3: Optimum
4: Only legionella
R/W
0: Continuous pump operation
1: Intermittent pump operation
2: No protection
0
0/1
R/W
0: No
1: Yes
0
1
0
R/W
1~10°C, step: 0,5°C
1°C
R/W
1~10°C, step: 0,5°C
3°C
R/W
0: No
1: Yes
R/W
0: Allowed
1: Not allowed
R/W
-15~35°C, step: 1°C
-4°C
R/W
0: Disabled
1: Enabled
R/W
-15~35°C, step: 1°C
0°C
R/W
0~20°C, step: 1°C
10°C
50
50
50
50
20
20
20
20
R/W
0~5
1: 1P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2)
1
R/W
2~20°C, step: 1°C
2°C
R/W
0~10°C, step: 1°C
2°C
R/W
0~10 kW, step: 0,2 kW
3 kW
R/W
0~10 kW, step: 0,2 kW
3 kW
R/W
0~10 kW, step: 0,2 kW
0 kW
0
0
0
R/W
2~20⁰C, step: 1⁰C
10⁰C
0
R/W
30~[6-0E]⁰C, step: 1⁰C
55⁰C
R/W
30~min(50, [6-0E])⁰C, step: 1⁰C
45⁰C
R/W
30~min(50, [6-0E])⁰C, step: 1⁰C
45⁰C
R/W
0: Reheat only
1: Reheat + Scheduled
2: Scheduled only
R/W
If [E-07]=0
40~75°C, step: 1°C
60°C
If [E-07]=5
40~80°C, step: 1°C
80°C
R/W
0~4⁰C, step: 1⁰C
0⁰C
R/W
2~40⁰C, step: 1⁰C
2⁰C
R/O
0: 1 LWT zone
1: 2 LWT zones
2.5
0
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
1 min
Installer setting at variance with