Installation Specifications

The following table shows the installation specifications of the FX700 main unit.
External dimensions
[mm]
Weight [kg](*3)
Air-conditioning
conditions
Altitude
Power conditions
*1
Includes the front cover
*2
Excludes protrusions (With protrusions included: 838.5 mm)
Table 3.1 Installation Specifications
Item
Width(*1)
Depth(*2)
Height
Maximum calorific value [kJ/h]
3
Exhaust volume [m
Recommended ambient temperature
/min]
Maximum
(*4)
Temperature and
Operating
humidity conditions
(*5)
Standby
Stopped(*7)
Temperature gradient
Humidity gradient
Noise [dB](*8,*9)
Sound power level [B](*9)
Allowable vibration
Operating (including standby)
2
[m/s
(gal)]
Stopped(*10)
Allowable dust concentration [mg/m
Operating [m]
Stopped [m](*6,*7)
Input voltage and phase
Frequency and variable width
Maximum power consumption [W]
Maximum apparent power [VA]
Power factor(*11)
Inrush current [A] [Rush time](*12)
Leakage current [mA](*13)
Temperature [°C]
Humidity [%RH]
Temperature [°C]
Humidity [%RH]
Temperature [°C]
Humidity [%RH]
3
]
22
Description
482.6
813
86.9 (2U)
41.8
9,803
5.5
7.8
5 to 35
20 to 80
5 to 40(*6)
20 to 80
0 to 50(*6)
8 to 80
15 [°C/Hr] or less
30 [%/day] or less
66
8.2
4.0 (400) (Synthetic seismic
wave)
10.0 (1,000) (Synthetic
seismic wave)
0.15
0 to 3,000
0 to 12,000
200 to 240 VAC ±10%
Single-phase
50/60 Hz +3/–3%
2,723
2,751
0.95 or more
30 or less