Mitsubishi Electric FR-F820-04750 Instruction Manual page 89

Hide thumbs Also See for FR-F820-04750:
Table of Contents

Advertisement

Installation and wiring
Safety stop function operation
Input
power
OFF
ON
Tab. 2-27:
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and
SD to use the inverter. (In the initial status, terminals S1 and PC, S2 and PC, and SIC and SD are
respectively shorted with shorting wires.)
If any of the protective functions shown in the following table is activated, the terminal SO turns
OFF.
Fault record
Option fault
Communication option fault
Parameter storage device fault
Retry count excess
Parameter storage device fault
Operation panel power supply
short circuit/
RS-485 terminal power supply
short circuit
Tab. 2-28:
If the internal safety circuit is operated normally, the terminal SO remains ON until E.SAF is
displayed, and the terminal SO turns OFF when E.SAF is displayed.
SA is displayed when the terminals S1 and S2 are identified as OFF due to the internal safety circuit
failure.
If another fault occurs at the same time as E.SAF, the other fault can be displayed.
If another warning occurs at the same time as SA, the other warning can be displayed.
For more details, refer to the Safety stop function instruction manual (BCN-A23228-001).
(Find a PDF copy of this manual in the CD-ROM enclosed with the product.
FR-F800
Internal
Input terminal
safety circuit
status
S1
Normal
ON
Normal
ON
Normal
OFF
Normal
OFF
Fault
ON
Fault
ON
Fault
OFF
Fault
OFF
Description of Safety stop function operation
Operation panel
indication
E.OPT
E.OP1
E.PE
E.RET
E.PE2
E.CTE
Indication of internal safety circuit failures
Output
,
Inverter
terminal
running status
S2
SO
Output shutoff
OFF
(Safe state)
ON
Drive enabled
ON
Output shutoff
OFF
OFF
(Safe state)
Output shutoff
ON
OFF
(Safe state)
Output shutoff
OFF
ON
(Safe state)
Output shutoff
ON
OFF
(Safe state)
Output shutoff
OFF
OFF
(Safe state)
Output shutoff
ON
OFF
(Safe state)
Output shutoff
OFF
OFF
(Safe state)
Fault record
24 V DC power fault
Safety circuit fault
Overspeed occurrence
CPU fault
Internal circuit fault
Control circuit
Operation panel indication
E.SAF
SA
Not displayed
Not displayed
Not displayed
Not displayed
Displayed
Displayed
Displayed
Displayed
Not displayed
Displayed
Displayed
Not displayed
Displayed
Displayed
Displayed
Displayed
Displayed
Displayed
Operation panel
indication
E.P24
E.SAF
E.OS
E.CPU
E.5 to E.7
E.13
2 - 61