Mitsubishi Electric FR-F820-04750 Instruction Manual page 551

Hide thumbs Also See for FR-F820-04750:
Table of Contents

Advertisement

Parameters
Connection diagram
● Basic system (Pr. 579 = "0")
- Sink logic
- Pr. 183 = 14
- Pr. 185 = 64
- Pr. 194 = 72
- Pr. 193 = 73
- Pr. 194 = 74
Power
supply
Forward rotation
Reverse rotation
PID control
PID forward/
reverse action
switchover
potentiometer
Fig. 5-186:
Prepare the power supply in accordance with the power supply specifications of the detector.
The applied output signal terminals differ by the settings of Pr. 190 to Pr. 196 (output terminal
function selection).
The applied input signal terminals differ by the settings of Pr. 178 to Pr. 189 (input terminal function
selection).
There is no need to input AU signal.
FR-F800
RST
STF
STR
RT(X14)
selection
JOG(X64)
SD
10
Setting
2
(Set point
setting)
5
1
4
(Measured value) 4 to 20 mA
0
Power supply
Connection diagram multi-pump function (basic system)
MC
RO4
RO3
RO2
Inverter
UVW
M1
MC RO2
(RO2)FU
MC RO3
(RO3)OL
MC RO4
(RO4)IPF
SE
24V
(A) Application parameters
Distributed water
M4
Pump 4
M3
Pump 3
M2
Pump 2
Pump 1
Supplied water
For 2-wire type
24 V DC
Detector
-
+
I003052E
5 - 389