(M) Monitor display and monitor output signal
Minus sign display for the monitors (Pr. 290)
● A negative output can be selected for the monitor display of the terminal AM (analog voltage
output), the operation panel, and a communication option. For a list of the monitors that can
output values with minus signs, refer to the monitor description list (on page 5-194).
Pr. 290 setting
0 (initial value)
⎯: Output without minus sign (positive values only)
Tab. 5-93:
● Select items to be displayed with minus signs using Pr. 1018 "Monitor with sign selection".
Types of monitor
Output frequency
Running speed
Motor torque
PID deviation
BACnet terminal AM output level
Remote output 1
Remote output 2
: Displayed with minus sign,
⎯: Displayed without minus sign (positive only)
Tab. 5-94:
Displayed without minus sign on the operation panel. Confirm the rotation direction with the
[FWD] or [REV] indicator.
NOTES
When terminal AM (analog voltage output) is "output with a minus sign", the output will be within
the –10 V DC to +10 V DC range. Connect the meter with which output level is matched.
Parameter unit (FR-PU07) displays only positive values.
5 - 204
Terminal AM output
1
Output with a minus sign
2
3
Output with a minus sign
4
5
Output with a minus sign
6
7
Output with a minus sign
Minus sign display for the monitors
Pr. 1018 setting
9999
Minus sign display using Pr. 1018
Operation panel display
Displayed with minus sign
Displayed with minus sign
Output with a minus sign
Output with a minus sign
Types of monitor
0
Remote output 3
Remote output 4
PID manipulated amount
Second PID deviation
Second PID manipulated amount
Control circuit temperature
Parameters
Negative indication on
communication options
Output with a minus sign
Output with a minus sign
Output with a minus sign
Output with a minus sign
Pr. 1018 setting
9999
0