Changing The Exercise Setting - Kohler 24RCLA Operation

Residential/light commercial generator sets
Table of Contents

Advertisement

7. Press Select to save the time and move to the next
screen.
8. Next Exercise is displayed. Use the up, down, and
select buttons to set the exercise time and date. Be
sure to set a time and date in the future.
9. Press Select. The controller exits the exercise
menu.
10. Press the Auto button and verify that the AUTO
LED is lit. The generator set must be in automatic
mode for the exercise to run as scheduled.
The exercise will run every 7 days at the same time,
starting on the date set. To change the exerciser to run
every other week or on a different day and time, use the
following procedure.
2.5.8

Changing the Exercise Setting

Set the date and time on the controller before setting the
exercise schedule. Set the exerciser to automatically
run the generator set for 20 minutes every week or every
two weeks. Follow the procedure below and see the
flowchart in Figure 2-3 to set the exercise time and date,
mode, and frequency.
Procedure to Change the Exercise Setting
1. Press the AUTO button on the controller.
2. Press the Select button to go to the main menu.
See Figure 2-2.
3. Press the down arrow button to step to the Genset
System menu.
4. Press the Select button to enter the Genset system
menu. See Figure 2-3.
5. Use the down arrow button to step to the next
Exercise menu.
TP-6905 9/21
6. Press the Select button. The setting flashes to
show that it can be changed. For example, the hour
flashes to show that the hour can be changed.
7. Press the UP or Down arrow buttons to change the
setting.
8. Press the Select button to save the setting and
move to the next. For example, save the hour
setting and move to minutes.
9. Repeat steps 5 through 8 to change the next item
on the line until the desired settings are displayed.
10. Press Select to save after all settings have been
selected. Settings will stop flashing.
11. If the generator set is connected to a Kohlerr Model
RXT transfer switch, the exercise can be changed
to a loaded exercise. Set the Exercise Mode to
loaded full speed, unloaded full speed, or unloaded
cycle as shown in Figure 2-3.
12. Set the exercise frequency (weekly or every two
weeks). Weekly exercises are recommended.
13. Press the down arrow button to step to the Return
menu. Press the Select button to return to the main
menu.
14. Check that the AUTO LED is lit. The generator set
must be in automatic mode for the exercise to run
as scheduled.
After a scheduled exercise run, the next exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Other transfer switches: For a loaded exercise with a
transfer switch other than a Kohlerr Model RXT,
program the exercise at the transfer switch controller.
Refer to the transfer switch operation manual for
instructions.